Customization: | Available |
---|---|
Type: | Distribution Metering Box |
Structure: | Protection |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main Application: The SF6 gas insulated switchgear (GIS) is used for receiving and distributing electric energy in power systems. It is widely used in various applications including:
Company Name: Guangdong Anhao Electrical Equipment Co., Ltd
Introducing the switchgear from Guangdong Anhao Electrical Equipment Co., Ltd:
Experience the reliability and safety of our switchgear for your electrical equipment needs.
12kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 42 | 42 | 42 | 42 | 42 | 42 |
Impulse Withstand Voltage | KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | 1250 | 630 | 630 | ||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 630 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 17.4 | |||||
Short Circuit Drop-out Current | KA | 31.5 | 25 | ||||
Making Capacity | KA | 50 | note | 63 | 63 | 63 | 63 |
Rated Short Time Withstand Current | KA/3S | 20 | 20 | 20 | 25 | 25 | |
Transfer Current | A | 1700 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 3000 | 10000 | 3000 |
24kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 24 | 24 | 24 | 24 | 24 | 24 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 65 | 65 | 65 | 65 | 65 | 65 |
Impulse Withstand Voltage | KV | 125 | 125 | 125 | 125 | 125 | 125 |
Rated Current | A | 630 | 125 | 630 | |||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 31.5 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 43.3 | |||||
Short Circuit Drop-out Current | KA | 20 | 20 | 25 | |||
Making Capacity | KA | 50 | 50 | 50 | 63 | 63 | |
Rated Short Time Withstand Current | KA/3S | 20 | 16 | 16 | 20 | 20 | |
Transfer Current | A | 1400 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 10000 | 10000 | 5000 |
Discover our Prefabricated 630A 1250A GIS Distribution Cabinet for efficient electric power supply. This SF6 Gas Insulated Equipment is ideal for medium voltage distribution systems.
Our product is designed to meet the following applicable conditions:
For more information, please contact Guangdong Anhao Electrical Equipment Co., Ltd.