Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | SF6 |
Installation: | Fixed |
Structure: | Lbs |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
NO. |
Items |
Unit |
Value |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated current |
A |
630 |
4 |
Rated short time withstand current |
kA |
20, 25 |
5 |
Rated peak withstand current |
kA |
50 |
6 |
Rated short circuit duration |
S |
4 |
7 |
Rated short circuit making current |
kA |
50 |
8 |
Theoretical operation |
Times |
10000 |
9 |
Main circuit resistance |
μΩ |
≤35 |
Suppliers with verified business licenses