Customization: | Available |
---|---|
Type: | Indoor Disconnect Switch |
Structure: | Protection |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applicable conditions
Type
|
GW4-40.5
|
GW4-72.5
|
GW4-126
|
GW4-126G
|
GW4-145
|
|
Rated voltage kV
|
40.5
|
72.5
|
126
|
126
|
145
|
|
Rated current A
|
630 1250
2000 2500 |
630 1250
2000 2500 |
630 1250
2000 2500 |
630 1250
|
1250 2000
2500 |
|
Short time withstand current ( rms) kA
|
20 31.5
40(46) |
20 31.5
40(46) |
20 31.5
40(46) |
20 31.5
|
20 31.5
40(46) |
|
Peak withstand current ( peak ) kA
|
50 80
100(104) |
50 80
100(104) |
50 80
100(104) |
50 80
|
50 80
100(104) |
|
Rated short-time power frequence withstand voltage ( rms ) kV
|
to each
|
80
|
140
|
185
(230) |
185
|
275
|
between breaks
|
110
|
160
|
210
(265) |
210
|
315
|
|
Lighting impulse withstand voltage ( peak ) kV
|
to each
|
185
|
325
|
450
(550) |
450
|
650
|
between breaks
|
215
|
375
|
520
(630) |
550
|
750
|
|
Horzontal force of terminal N
|
550
(750) |
735-750
|
1000
|
1000
|
1500
|
|
Weigh of signle pole kg
|
80
|
200
|
240
|
300
|
3
|