• Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
  • Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
  • Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
  • Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
  • Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
  • Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear

Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear

Type: Load Break Switch
Structure: Protection
Certification: ISO9001:2000, CCC
Form: Partly-welded Type
Operation Voltage: High Voltage
Size: 1 Uint
Samples:
US$ 1500/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
FZN25
Application Range
Rmu Switchgear
Shell Material
Stainless Steel
Brand
Anhao
Rated Current
630A
Rated Voltage
12kv
Rated Frequency
50Hz
Poles Number
3
MOQ
1PCS
Transport Package
Wooden Case
Trademark
ANHAO
Origin
China
Production Capacity
50pieces/Week

Product Description

FZN25 12kv Indoor High Voltage Load Break Switch for Switchgear

Fzn25 12kv Indoor High Voltage Load Break Switch for SwitchgearFzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
Product Information 
It is used in the ring network city distribution and industrial equipment of 12KV and three-phase AC 50Hz to control load and short-circuit. Because of the switch with fuse protecting transformer etc more reliably than circuit breaker. It is especially suitable for ring network cloud radial distribution and package substation.
 

Applicable conditions

  • Altitude: ≤1000m
  • Ambient air temperature: not higher than +40°C, not lower than-25°C
  • Relative humidity: the daily mean is not more than 95%, monthly mean is not more than 90%
  • Earthquake intensity: not more than 8°
  • No fire, explosion hazard, chemical etching and intense vibration
  • Pollution grade: II
  • Ambient air shouldn't be polluted by corrosive or flammable gas and vapor.
    (Note: Spring operating mechanism has electric and manual types)

Outline Mounting Dimensions
    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    Technical Parameters 
    Products with special requirements, specifications, and dimensions that need to be improved can be designed and manufactured according to user requirements.
     
    NO.
    Items
    Unit
    Data
    FZN25-12D/T630-20
    FZRN25-12D/T125-31.5
    1
    Rated voltage
    KV
    12
    2
    Rated frequency
    Hz
    50
    3
    Rated Current
    A
    630
    200
    4
    Rated insulation level
    1 min power frequency withstanded insulation voltage
    KV
    Arc chamber between open contacts 30: To earth, phase to phase 42;Isolation between open contacts 48
    Lightning impulse withstand voltage
    KV
    To earth phase to phase 75: solation between open contact 85
    5
    Rated short-time withstand current
    KA
    20
     
    6
    Rated short circuit duration
    S
    4
     
    7
    Rated peak withstand curent
    KA
    50
     
    8
    Rated active load breaking current
    A
    630
     
    9
    Rated closed-loop breaking current
    A
    630
     
    10
    Rated cable charging breaking current
    A
    10
    11
    Rated breaking no-load transformer capacity
    KVA
    1600
    12
    Rated short-circuit breaking current
    KA
    -
    31.5
    13
    Rated transfer current
    A
     
    2000
    14
    Fuse Type
     
     
    SDLAJ-12 XPNT1-12
    15
    IImpactor output energy
    J
     
    1+0.5
    16
    Rated short circuit dosing current
    KA
     
    80 (expected peak)
    17
    Earthing switch rated short-fime withstand current
    KA
    20
    18
    Earthing switch rated short circuit duration
    S
    2
    19
    Earthing switch rated peak withstand current
    KA
    50
    20
    Auxiliary circuit rated voltage
    V
    ≈220V,≈110V
    21
    Mechanical life
    Times
    1000
    Detail Images
    Fzn25 12kv Indoor High Voltage Load Break Switch for SwitchgearFzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    NOTES: Supports OEM, so there are other sizes or material requirements that can be produced according to requirements


    Company Profile
    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    Workshop Corner
    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    Testing Equipment

    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear


    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear
    Fzn25 12kv Indoor High Voltage Load Break Switch for Switchgear


    FAQ
    Q: Are you a trading company or manufacturer?
    A: We are factory with more than 20 years of experience in this field.

    Q: Can I get a sample before the bulk order?
    A: Yes, we welcome sample orders to test and check quality. Mixed samples are
    acceptable.
     
    Q: Can we print our logo/ company name on products?
    A: Yes, of course, we accept OEM, then need you to provide brand authorization to us
     
    Q: Do you accept product customization?
    A: Yes, of course, please provide specific drawings or parameters, we will quote you after the evaluation
     
    Q: How long is your delivery time?
    A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days. if the goods are not in stock, it is according to the quantity

    Q: How to solve quality problems after sales?
    A: Take photos of the quality problems and send them to us for our checking and confirmation, we will make a satisfactory solution for you within 3 days.
     
    Q: What are your terms of payment?
    A: 30% T/T in advance, balance before shipment.

    Send your message to this supplier

    *From:
    *To:
    *Message:

    Enter between 20 to 4,000 characters.

    This is not what you are looking for? Post a Sourcing Request Now

    You Might Also Like

    Diamond Member Since 2021

    Suppliers with verified business licenses

    Manufacturer/Factory
    Number of Employees
    85
    Year of Establishment
    2014-04-01