Customization: | Available |
---|---|
Type: | Outdoor Vacuum Circuit Breaker |
Structure: | Protection |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applicable conditions
number | project | unit | data | ||
01 | The rated voltage | kV | 12 | ||
02 | Rated insulation level | 1min power frequency withstand voltage | Dry test (ground, inter-pole/fracture) | kV | 42/48 |
Try the wet | 34 | ||||
Lightning shock withstand (peak, pole/fracture) | 75/85 | ||||
03 | Rated current | A | 630 | ||
04 | Rated short-circuit breaking current | kA | 20 | ||
05 | Rated order of operation | 0-0.3-C0-180S-COS | |||
06 | Rated short-circuit breaking current Times of breaking | 30 | |||
07 | Rated short circuit closing current (peak value) | times | 50 | ||
08 | Rated peak tolerance current | kA | |||
09 | Rated short-time withstand current | kA | 20 | ||
10 | Rated short circuit duration | kA | 4 | ||
11 | Switching time (the time from receiving the switching order from the control unit to the separation of three-phase contacts) | s | 0.040-0.060 | ||
12 | Closing time (the time from the control unit receiving the closing order to the three phase contact closing) | s | 0.070-0.120 | ||
13 | Mechanical life | times | 10000 | ||
14 | Rated switching operating voltage | V | DC110,DC220 | ||
15 | Rated switching operating voltage | V | DC110,DC220 | ||
16 | Over current protection | Current setting multiple | 0.2~0.5 | ||
Set current allowance | ±10% | ||||
Delay setting | s | 0~5 | |||
Delay tolerance | ±10% | ||||
Current setting multiple | 2.5~10 | ||||
17 | Quick break protection | Set current allowance | ±10% | ||
Delay setting | s | 0~0.5 | |||
Delay tolerance | ±10% | ||||
18 | Control unit AC charging | rating | A | 5 | |
19 | Input current | Range | A | 0.5~8 |