Main Application: The SF6 gas insulated switchgear (GIS) is designed for receiving and distributing electric energy in power systems. It is commonly used in various applications such as:
Company Name: Guangdong Anhao Electrical Equipment Co., Ltd
Introducing the switchgear from Guangdong Anhao Electrical Equipment Co., Ltd:
Experience the reliability and safety of our switchgear for your electrical equipment needs.
12kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 42 | 42 | 42 | 42 | 42 | 42 |
Impulse Withstand Voltage | KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | 1250 | 630 | 630 | ||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 630 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 17.4 | |||||
Short Circuit Drop-out Current | KA | 31.5 | 25 | ||||
Making Capacity | KA | 50 | note | 63 | 63 | 63 | 63 |
Rated Short Time Withstand Current | KA/3S | 20 | 20 | 20 | 25 | 25 | |
Transfer Current | A | 1700 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 3000 | 10000 | 3000 |
24kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 24 | 24 | 24 | 24 | 24 | 24 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 65 | 65 | 65 | 65 | 65 | 65 |
Impulse Withstand Voltage | KV | 125 | 125 | 125 | 125 | 125 | 125 |
Rated Current | A | 630 | 125 | 630 | |||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 31.5 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 43.3 | |||||
Short Circuit Drop-out Current | KA | 20 | 20 | 25 | |||
Making Capacity | KA | 50 | 50 | 50 | 63 | 63 | |
Rated Short Time Withstand Current | KA/3S | 20 | 16 | 16 | 20 | 20 | |
Transfer Current | A | 1400 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 10000 | 10000 | 5000 |