Main Application
The SF6 gas insulated switchgear (GIS) is used for receiving and distributing electric energy in power systems. It is widely used in various applications including:
Company Name: Guangdong Anhao Electrical Equipment Co., Ltd
For more information, visit Guangdong Anhao Electrical Equipment Co., Ltd website.
12kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 42 | 42 | 42 | 42 | 42 | 42 |
Impulse Withstand Voltage | KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | 1250 | 630 | 630 | ||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 630 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 17.4 | |||||
Short Circuit Drop-out Current | KA | 31.5 | 25 | ||||
Making Capacity | KA | 50 | note | 63 | 63 | 63 | 63 |
Rated Short Time Withstand Current | KA/3S | 20 | 20 | 20 | 25 | 25 | |
Transfer Current | A | 1700 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 3000 | 10000 | 3000 |
24kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 24 | 24 | 24 | 24 | 24 | 24 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 65 | 65 | 65 | 65 | 65 | 65 |
Impulse Withstand Voltage | KV | 125 | 125 | 125 | 125 | 125 | 125 |
Rated Current | A | 630 | 125 | 630 | |||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 31.5 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 43.3 | |||||
Short Circuit Drop-out Current | KA | 20 | 20 | 25 | |||
Making Capacity | KA | 50 | 50 | 50 | 63 | 63 | |
Rated Short Time Withstand Current | KA/3S | 20 | 16 | 16 | 20 | 20 | |
Transfer Current | A | 1400 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 10000 | 10000 | 5000 |
Discover our 630A 1250A Box Type Substation Power Supply Unit, perfect for your power distribution needs. This unit features SF6 gas insulation and a range of essential components.
Company Name: Guangdong Anhao Electrical Equipment Co., Ltd
Guangdong Anhao Electrical Equipment Co., Ltd specializes in manufacturing 630A and 1250A Box Type Substation Power Supply Units, including Ring Main Units, SF6 Gas Insulated products, Distribution Transformers, and various Switchgear Cabinets.
Explore our 630A 1250A Box Type Substation Power Supply Unit for all your testing needs. From prefabricated substations to circuit breakers, we have you covered.