Type: | Distribution Metering Box |
---|---|
Structure: | Protection |
Certification: | ISO9001:2000, CCC |
Form: | Partly-welded Type |
Operation Voltage: | High Voltage |
Size: | 1 Uint |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Main Application
The SF6 gas insulated switchgear (GIS) is used for receiving and distributing electric energy in power systems. It is widely used in various applications including:
Company Name: Guangdong Anhao Electrical Equipment Co., Ltd
Introducing the switchgear from Guangdong Anhao Electrical Equipment Co., Ltd:
12kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 42 | 42 | 42 | 42 | 42 | 42 |
Impulse Withstand Voltage | KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | 1250 | 630 | 630 | ||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 630 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 17.4 | |||||
Short Circuit Drop-out Current | KA | 31.5 | 25 | ||||
Making Capacity | KA | 50 | note | 63 | 63 | 63 | 63 |
Rated Short Time Withstand Current | KA/3S | 20 | 20 | 20 | 25 | 25 | |
Transfer Current | A | 1700 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 3000 | 10000 | 3000 |
24kv Technical Parameter | Unit | C module | F module | V module | CB module | ||
Load break switch |
Switch fuse |
Vacuum circuit breaker |
Isolate/ earthing switch |
Vacuum circuit breaker |
Isolate/ earthing switch |
||
Rated Voltage | KV | 24 | 24 | 24 | 24 | 24 | 24 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequence Withstand Voltage | KV | 65 | 65 | 65 | 65 | 65 | 65 |
Impulse Withstand Voltage | KV | 125 | 125 | 125 | 125 | 125 | 125 |
Rated Current | A | 630 | 125 | 630 | |||
Closed Loop | A | 630 | |||||
Off Load Cable Charging | A | 10 | |||||
Rated Active Load Drop-oput Current | A | 31.5 | 630 | ||||
When Earth Fault Frop out Current of Cable Charging | A | 43.3 | |||||
Short Circuit Drop-out Current | KA | 20 | 20 | 25 | |||
Making Capacity | KA | 50 | 50 | 50 | 63 | 63 | |
Rated Short Time Withstand Current | KA/3S | 20 | 16 | 16 | 20 | 20 | |
Transfer Current | A | 1400 | |||||
Loop Resistance | μΩ | ≤300 | ≤600 | ||||
Mechanical Life | Times | 5000 | 5000 | 10000 | 10000 | 10000 | 5000 |